TitleProduct

3240 Epoxy Board Transformer Insulated Epoxy Board

  • Price:

    Negotiable

  • minimum:

  • Total supply:

  • Delivery term:

    The date of payment from buyers deliver within days

  • seat:

    Shaanxi

  • Validity to:

    Long-term effective

  • Last update:

    2021-02-16 11:39

  • Browse the number:

    64

Send an inquiries

Company Profile

St.Qin Cross Boarder E-Commerce Co., Ltd

By certification [File Integrity]

Contact:daqinyun(Mr.)  

Email:

Telephone:

Phone:

Area:Shaanxi

Address:Shaanxi

Website:http://www.jhd-material.com/ http://daqinyun.chengximianfang.com/

Product Details

Production Description

3240 Epoxy Board Transformer Insulated Epoxy Board is a combination of alkali-free glass fiber, epoxy resin and phenolic resin with the process of laminating, heat and pressure. It could be used for insulating structural parts in electrical and other industries. Also, Insulation Board 3240 is a good choice for Electrical Winding Insulation, Winding Wire Coating Insulation, Electrical Base, Shell, Motor, Switch Baseplate.


Properties

Insulating Material 3240 Epoxy Sheet has high mechanical and electrical strength, excellent rigidity, good dimensional stability, great dielectric property, low water absorption, stable electric insulation performance. All the amazing properties make the material to be one of the most popular materials in various industries.


Technical Data for 3240 GradeB

NO

TEST ITEMS

UNIT

TEST RESULT

TEST METHOD

1

Density

g/cm3

2.07

GB/T 1303.2-2009

2

Water Absorption

mg

6.0

3

Bending Strength Perpendicular to Laminations

A

MPa

203

B

192

4

Modulus of Elasticity in Flexure

A

MPa

2.12*104

B

2.38*104

5

Parallel Layer Impact Strength

(Simply Supported Beam, Gap)

A

KJ/m²

47.4

B

35.8

6

Parallel Layer Shear Strength

A

MPa

49.8

B

52.7

7

Tensile Strength

A

MPa

147

B

121 o

8

Compressive Strength Perpendicular to Laminations compressive

MPa

438

9

Insulation Resistance after Soaking

Ω

2.0*109

10

Vertical Layer Breakdown Voltage (90℃ + 2℃ oil, 20s step by step boost)

MV/m

8.6

11

Parallel Layer Breakdown Voltage (90℃ + 2℃ oil, 20s step by step boost)

kV

28.0

12

Flammability

-

V-1

13

Deflection Temperature under Load

A

>140

B

>140

14

Adhesive Strength

N

6324

GB/T 1303.6-2009

REMARK:

1. NO.2 the sample size is 50mm*50mm*50mm;

2. NO.8 the sample height is (9.05~9.56) mm;

3. NO.10 the sample thickness is (2.91~2.95)mm;

4. NO.11 the sample size is 100.00mm*5.08mm*24.10mm;


It can be machined to various shapes as insulation parts in which the mechanical and electrical properties is required.


Factory

two environmental control equipment used for the cyclic utilization of exhaust gas incineration afterheat six domestically most advanced gum-dipping drying production equipment


Packaging and Shipping

Regular packing, Protect by Pallet

http://www.jhd-material.com/